ECO 65 GC 2
- Two-stage operation,
- Ability to work with natural gas and LPG fuel,
- Operation at 21 mbar gas pressure up to 300 mbar and ECO 55 GC 2 model,
- Wide thermal capacity adjustment range according to heat requirement,
- Direct ignition and optional pilot ignition option,
- Flame control with ignition and ionization electrode,
- Control of sufficient gas pressure with minimum gas pressure switch,
- Unique combustion head with high combustion efficiency and uniform fuel mixture,
- Control of combustion air with air pressure switch,
- Working at low noise levels with its aluminum alloy, lightweight body,
- Minimum friction losses in the body and combustion head,
- Combustion air flow adjustment with internal fan damper,
- Easy access to all parts without removing the burner from the boiler,
- Sliding flange for connection to different boiler types,
- Compact design requiring minimum maintenance,
- Environmentally friendly with low NOx and CO emissions.
Burner Type | Capacity | Capacity | Natural Gas Consumption | LPG Consumption | Fan Motor Power | Voltage at 50 Hz | ||||
---|---|---|---|---|---|---|---|---|---|---|
Minimum kcal/h | Maximum kcal/h | Minimum kW | Maximum kW | Minimum Nm³/h | Max. Nm³/h | Minimum Nm³/h | Max. Nm³/h | kW | VAC | |
ECO 65 GC 2 | 430,000 | 3,010,000 | 500 | 3500 | 52.12 | 364.85 | 19.11 | 133.78 | 5.5 | 3N 400 |